  • Abstract
    Achievable generator reactive capability (GRC) is generally much less than indicated by manufacturers´ reactive capability curves, due to constraints imposed by plant auxiliaries and the power system itself. The nature of these constraints is explained and a method for calculating them is provided and verified by field tests on a unit at high and low power system voltage levels. Several recommendations are made to enhance the GRC of the tested unit
  • Keywords
    machine testing; machine theory; reactive power; synchronous generators; LV; field tests; generator reactive capability; power system; reactive capability limitation; recommendations; synchronous machines; Manufacturing; Power generation; Power systems; Reactive power; Samarium; Stability; Stators; Synchronous machines; Testing; Voltage;