Evaluation of Switching Surge Overvoltages on Medium Voltage Power Systems
Author
Perkins, J.F.
Author_Institution
Westinghouse Electric Corporation, Switchgear Division
Issue
6
fYear
1982
fDate
6/1/1982 12:00:00 AM
Firstpage
1727
Lastpage
1734
Abstract
The increasing application of vacuum circuit-breakers on utility and industrial systems has prompted a renewed and detailed investigation of vacuum switching surge mechanisms. The present paper discusses the mechanisms of switching surge phenomena, and describes how a test-validated computer program is used to establish a thorough understanding of breaker/system interaction. The program uses data on the circuit-breakers derived from several thousand measurements to determine the effects of cable length, surge protection, and MVA rating on switching overvoltage cumulative appearance probabilities of motor and transformer loads.
Keywords
Application software; Circuit testing; Industrial power systems; Length measurement; Medium voltage; Power systems; Surge protection; Switching circuits; System testing; Vacuum systems;