Switching Surges and Arrester and Gap Performance during 200-Kv Line-Dropping Tests
Author
Rothenbuhler, W.N. ; Wilson, D.D.
Volume
81
Issue
3
fYear
1962
fDate
4/1/1962 12:00:00 AM
Firstpage
312
Lastpage
319
Abstract
A series of line-dropping field tests on the 220-kv Saugus-Santa Clara transmission line of the Southern California Edison Company indieated unexplained circuit breaker bushing-gap sparkover and abnormally low lightning arrester sparkover on surges caused by circuit breaker restriking. The portion Bf seqweynte test was set up on a system in miniature to facilitate interpretation and analysis of the field results and verify measurement techniques. Significant data pertaining to the nature of surge voltages and lightning arrester and bushing-gap performance are presented.
Keywords
Arresters; Circuit faults; Induction motors; Inductors; Resonance; Surges; Switches; Testing; Transient analysis; Voltage;