Abstract
The paper reviews the application of autoreclosure to extra-high-voltage (EHV) transmission systems and examines the relative merits of 3-phase and singlephase autoreclosure. Laboratory experiments for determining the behavior of the residual are during single-phase autoreclosure are described, and results given of tests at a switchgear test plant simulating conditions for 270 miles of 330-kv line. Corroborative field tests and system operating experience are recorded indicating satisfactory performance of single-phase autoreclosure on 330-kv lines up to 200 miles long.
Keywords
Circuit breakers; Circuit faults; Circuit stability; Delay; Hazards; Laboratories; Power generation; Switchgear; Testing; Voltage;
fLanguage
English
Journal_Title
Power Apparatus and Systems, Part III. Transactions of the American Institute of Electrical Engineers
Publisher
ieee
ISSN
0097-2460
Type
jour
DOI
10.1109/AIEEPAS.1962.4501473
Filename
4501473
Link To Document