• DocumentCode
    1173691
  • Title

    Failure Analysis Of Synathetic Insulators With Fiberglass Rod Submitted To Mechanical Loads

  • Author

    Mier-Maza, R. ; Lanteigne, J. ; de Tourreil, C.

  • Author_Institution
    Hydro Quebec Institute of Research
  • Issue
    9
  • fYear
    1983
  • Firstpage
    3123
  • Lastpage
    3130
  • Abstract
    Four end fitting designs of long rod fiberglass core suspension insulators are studied and the failure mechanisms are analyzed after UTS and creep tests. The fracture occurs in the fiberglass rod due to the stresses induced by the metal part of the endfitting that hold the insulating components.
  • Keywords
    Creep; Failure analysis; Fitting; Glass; Insulation; Insulator testing; Optical fiber testing; Power transmission lines; Stress; Voltage;