• DocumentCode
    1175097
  • Title

    Switching Tests on Grounding Switches for Gas Insulated Substations

  • Author

    Kugler, R. ; Luehrmann, H.M. ; Veuhoff, F.

  • Author_Institution
    SIEMENS AG
  • Issue
    12
  • fYear
    1984
  • Firstpage
    3569
  • Lastpage
    3572
  • Abstract
    The paper deals with an investigation on the capacitive and inductive switching capability of grounding switches, as required for parallel HVAC transmission lines with one circuit carrying the current while the other is grounded at both ends. When the grounding switches are opened, they have to interrupt both the induced inductive current, and the current coupled capacitively. In addition, they have to withstand the transient recovery voltage (TRV).
  • Keywords
    Circuit testing; Coupling circuits; Distributed parameter circuits; Gas insulated transmission lines; Gas insulation; Grounding; Substations; Switches; Switchgear; Switching circuits;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1984.318388
  • Filename