DocumentCode
1175650
Title
An Alternative Approach to Adaptive Single-Pole Auto Reclosing in High-Voltage Transmission Systems Based on Variable Dead Time Control
Author
Ahn, S. P. ; Aggarwal, R. K. ; Johns, A. T.
Author_Institution
Sungkyunkwan University, Korea; University of Bath, Bath, U.K.
Volume
21
Issue
4
fYear
2001
fDate
4/1/2001 12:00:00 AM
Firstpage
70
Lastpage
70
Abstract
This paper presents a new concept, based on variable dead time control, in adaptive single-pole auto reclosing (SPAR). The proposed scheme can give rise to a high rate of successful reclosing by adapting to variable dead times. The significance of this algorithm is that it uses the waveform patterns of the voltage transients following initial breaker opening. The performance of this proposed method is tested under a variety of fault locations on the Korean 765 kV system, and the outcome of the study clearly indicates that variable dead time auto-reclosing scheme can be used as an attractive and effective means of better management and operation of a high-voltage transmission system.
Keywords
Adaptive control; Control systems; Cost function; Evolutionary computation; Optimization methods; Power system modeling; Power system planning; Power transmission; Programmable control; System testing; Adaptive single-pole auto reclosing; dead time control; high-voltage transmission lines;
fLanguage
English
Journal_Title
Power Engineering Review, IEEE
Publisher
ieee
ISSN
0272-1724
Type
jour
DOI
10.1109/MPER.2001.4311325