DocumentCode
1178532
Title
Current for Design of Grounding Systems
Author
Thapar, B. ; Madan, Sunil K.
Author_Institution
Punjab Engineering College
Issue
9
fYear
1984
Firstpage
2633
Lastpage
2638
Abstract
A simple method to estimate the current for calculating the size of the grounding conductor and for evaluating the step, touch and transferred potentials, is presented. The factors effective in making these currents different from the total fault current have been indicated. Various types of substations, different fault locations and a wide rangeof parameters of aerial ground wire encountered in practice are considered. Data presented emphasizes the saving in grounding design costs that can be realised by using maximum realistic ground currents rather than maximum calculated total fault currents for evaluation of step & touch potentials.
Keywords
Conductors; Current supplies; Educational institutions; Fault currents; Fault location; Grounding; Power transmission lines; Soil; Substations; Wires;
fLanguage
English
Journal_Title
Power Apparatus and Systems, IEEE Transactions on
Publisher
ieee
ISSN
0018-9510
Type
jour
DOI
10.1109/TPAS.1984.318235
Filename
4112868
Link To Document