DocumentCode
1178952
Title
New Short-Circuit Testing Facilities to Cope With the Recent Development of GIS
Author
Yamamoto, M. ; Yamashita, S. ; Ikeda, H. ; Yanabu, S.
Author_Institution
Toshiba Corporation
Issue
1
fYear
1985
Firstpage
150
Lastpage
156
Abstract
Short-circuit testing facilities are discussed for SF6 gas-insulated switchgear (GIS) equipment. It is shown that the supply voltage of 28kV will suffice to supply short-circuit current up to 80kA without severe distortions for four breaks used in the full voltage test of a tank-type SF6 gas circuit breaker (GCB). A new testing method using two transformers is proposed for a three-phase-in-one-tank-type GCB.
Keywords
Circuit breakers; Circuit testing; Dielectrics; Gas insulation; Geographic Information Systems; Substations; Sulfur hexafluoride; Switches; Switchgear; Voltage;