• DocumentCode
    1180662
  • Title

    Evaluation Of Partial Discharge Measurement Circuits And Associated Calibration Techniques

  • Author

    Huang, S.J. ; Lowder, S.M. ; Sarkinen, S.H. ; Chartier, V.L.

  • Author_Institution
    Wuhan High Voltage Research Institute
  • Issue
    2
  • fYear
    1985
  • Firstpage
    407
  • Lastpage
    415
  • Abstract
    This paper presents an evaluation of the RIV circuits used for the measurement of partial discharges. The results show that the NEMA 107-1964 RIV circuit, as presently used in high voltage laboratories, does not consider the entire calibration problem. The test circuit can produce resonance at a particular frequency, the choke coils can create a resonance shift, and the capacitance from the bottom end of the coupling capacitor to ground is significant. This capacitance, combined with the coupling capacitor and inductance of the conductor, forms a resonant circuit at the measurement frequencies.
  • Keywords
    Calibration; Capacitance; Capacitors; Circuit testing; Coupling circuits; Frequency; Partial discharge measurement; Partial discharges; RLC circuits; Resonance;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1985.319056
  • Filename
    4113096