• DocumentCode
    1182407
  • Title

    Simulation of the SF6 Arc Behavior by a Cylindrical Arc Model

  • Author

    Tanabe, T. ; Ibuki, K. ; Sakuma, S. ; Yonezawa, T.

  • Author_Institution
    Itami Works, Mitsubishi Electric corporation
  • Issue
    7
  • fYear
    1985
  • fDate
    7/1/1985 12:00:00 AM
  • Firstpage
    1903
  • Lastpage
    1909
  • Abstract
    The dependece of the arc characteristics on the background SF6 gas condition is studied in detail. High (ph) value of SF6 gas at a temperature of 2000 K plays an important role for the peculiar behaviors of the SF6 arcs. The simulation by the cylindrical arc model[1] shows that the temperature profile across the arc is steep in the current decreasing phase and becomes broad in the current increasing phase. The time evolution of the current and voltage of the SF6 gas arc is interpreted into a curve on a (1/R) (dR/dt)-(ei) plane. The simulation results by the cylindrical arc model are plotted on the (l/R)(dR/dt)-(ei) plane to compare them with the experimental results. The cylindrical arc model gives a better similarity to the actual arc than Mayr´s model in the current decreasing phase.
  • Keywords
    Circuit simulation; Cooling; Differential equations; Energy exchange; Fluid flow; Hydrogen; Sulfur hexafluoride; Temperature dependence; Temperature distribution; Temperature measurement;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1985.319183
  • Filename