• DocumentCode
    1183401
  • Title

    Load and Voltage Balancing in Harmonic Power Flows by Means of Static VAr Compensators

  • Author

    Mayordomo, J. G. ; Izzeddine, Mohamed ; Asensi, Rafael

  • Author_Institution
    Universidad Politecnica de Madrid, Madrid, Spain
  • Volume
    22
  • Issue
    4
  • fYear
    2002
  • fDate
    4/1/2002 12:00:00 AM
  • Firstpage
    80
  • Lastpage
    80
  • Abstract
    In special applications, static VAr compensators (SVC) with thyristor controlled reactors (TCR) are used to balance unbalanced loads or to eliminate voltage unbalances at the terminals of the SVC. In both cases, load balancing and voltage balancing, the TCR can present a significant unbalanced behavior that produces important quantities of noncharacteristic harmonics. In this paper, the formulation and solution of the load and voltage balancing problems are developed for harmonic power flows obtained from a combination of two blocks: a conventional load flow (CLF) and an iterative harmonic analysis (IHA). In both blocks, the treatment of load and voltage balancing is described in detail. Load flow calculations and harmonic analysis show the presence of noncharacteristic harmonics in these two situations.
  • Keywords
    Abstracts; Harmonic analysis; Inductors; Industrial power systems; Load flow; Load management; Power system harmonics; Static VAr compensators; Thyristors; Voltage control;
  • fLanguage
    English
  • Journal_Title
    Power Engineering Review, IEEE
  • Publisher
    ieee
  • ISSN
    0272-1724
  • Type

    jour

  • DOI
    10.1109/MPER.2002.4312159
  • Filename