DocumentCode
1183401
Title
Load and Voltage Balancing in Harmonic Power Flows by Means of Static VAr Compensators
Author
Mayordomo, J. G. ; Izzeddine, Mohamed ; Asensi, Rafael
Author_Institution
Universidad Politecnica de Madrid, Madrid, Spain
Volume
22
Issue
4
fYear
2002
fDate
4/1/2002 12:00:00 AM
Firstpage
80
Lastpage
80
Abstract
In special applications, static VAr compensators (SVC) with thyristor controlled reactors (TCR) are used to balance unbalanced loads or to eliminate voltage unbalances at the terminals of the SVC. In both cases, load balancing and voltage balancing, the TCR can present a significant unbalanced behavior that produces important quantities of noncharacteristic harmonics. In this paper, the formulation and solution of the load and voltage balancing problems are developed for harmonic power flows obtained from a combination of two blocks: a conventional load flow (CLF) and an iterative harmonic analysis (IHA). In both blocks, the treatment of load and voltage balancing is described in detail. Load flow calculations and harmonic analysis show the presence of noncharacteristic harmonics in these two situations.
Keywords
Abstracts; Harmonic analysis; Inductors; Industrial power systems; Load flow; Load management; Power system harmonics; Static VAr compensators; Thyristors; Voltage control;
fLanguage
English
Journal_Title
Power Engineering Review, IEEE
Publisher
ieee
ISSN
0272-1724
Type
jour
DOI
10.1109/MPER.2002.4312159
Filename
4312159
Link To Document