DocumentCode
1184954
Title
Sound intensity of the Comerford HVDC converter station
Author
Kendig, R.P.
Author_Institution
Westinghouse Res. & Dev. Center, Pittsburgh, PA, USA
Volume
4
Issue
3
fYear
1989
fDate
7/1/1989 12:00:00 AM
Firstpage
1876
Lastpage
1881
Abstract
The author demonstrates acoustic intensity for in situ sound power measurements of converter-type transformers and rank-orders all other noise sources at the Comerford high-voltage DC converter station. The sound intensity measurement uses two closely-spaced, phase-matched pressure-sensitive microphones to approximate one component of the intensity vector. Measurements made at the Comerford station are used with geometrical considerations and Gauss´ law to compute individual noise source strengths despite interference and reverberation. The data and analyses show that over 84% of the noise is radiated by harmonic filters. Another 12% can be traced to the converter transformers. The analysis also shows that noise levels increase in loaded vs. unloaded converter transformers by nearly four times. The results support the claim that sound intensity has applications in the power distribution industry as a diagnostic tool for quantifying transformer noise. The results also indicate where noise reduction efforts should be concentrated at the Comerford station
Keywords
DC power transmission; acoustic intensity measurement; power transformers; Comerford HVDC converter station; acoustic intensity; converter-type transformers; harmonic filters; noise sources; phase matched microphones; pressure-sensitive microphones; reverberation; sound intensity measurement; sound power measurements; Acoustic measurements; Acoustic noise; DC-DC power converters; Frequency conversion; HVDC transmission; Microphones; Noise measurement; Phase measurement; Power measurement; Transformers;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/61.32685
Filename
32685
Link To Document