DocumentCode
1186026
Title
Lightning induced disturbances in buried cables - part II: experiment and model validation
Author
Paolone, M. ; Petrache, E. ; Rachidi, F. ; Nucci, C.A. ; Rakov, V.A. ; Uman, M.A. ; Jordan, D. ; Rambo, K. ; Jerauld, J. ; Nyffeler, M. ; Schoene, J.
Author_Institution
Dept. of Electr. Eng., Univ. of Bologna, Italy
Volume
47
Issue
3
fYear
2005
Firstpage
509
Lastpage
520
Abstract
This paper presents experimental results obtained at the International Center for Lightning Research and Testing (ICLRT) at Camp Blanding, Florida during the summers of 2002 and 2003. Currents induced by triggered and natural lightning events were measured at the terminations of a buried power cable, in the cable shield, and in the inner cable conductor. Measurements of the horizontal component of the magnetic field above the ground surface for both natural and triggered lightning are also presented. For distant natural lightning events, locations of ground strike points were determined using the U.S. National Lightning Detection Network (NLDN). Based on the theoretical developments presented in Part I of this paper , the field-to-buried cable coupling equations are solved in both the time domain and in the frequency domain. The obtained experimental results are then used to validate the numerical simulations provided by the relevant developed codes.
Keywords
cable shielding; electromagnetic coupling; frequency-domain analysis; lightning; numerical analysis; power cables; time-domain analysis; underground cables; Camp Blanding; Florida; International Center for Lightning Research and Testing; US National Lightning Detection Network; buried power cables; cable shield; field-to-buried cable coupling equations; frequency-domain solution; inner cable conductor; lightning induced disturbances; magnetic field measurements; natural lightning; time domain solution; triggered lightning; Conductors; Current measurement; Equations; Frequency domain analysis; Lightning; Magnetic field measurement; Magnetic shielding; Power cables; Power measurement; Testing; LEMP-to-buried cables electromagnetic coupling; power cables; power system lightning effects; underground power distribution lines;
fLanguage
English
Journal_Title
Electromagnetic Compatibility, IEEE Transactions on
Publisher
ieee
ISSN
0018-9375
Type
jour
DOI
10.1109/TEMC.2005.853163
Filename
1516222
Link To Document