DocumentCode
1189497
Title
Development of 500-kV XLPE cables and accessories for long distance underground transmission lines-Part II: jointing techniques
Author
Kubota, Takeo ; Takahashi, Yoshihisa ; Hasegawa, Takaaki ; Noda, Hajime ; Yamaguchi, Masayuki ; Tan, Masayuki
Author_Institution
Tokyo Electr. Power Co. Inc., Japan
Volume
9
Issue
4
fYear
1994
fDate
10/1/1994 12:00:00 AM
Firstpage
1750
Lastpage
1759
Abstract
This paper reports on the results of a basic inquiry for the purpose of developing extrusion-molded joints (EMJ) for use with 500 kV XLPE power cable. The authors have made it clear that the factors that govern EMJ performance, like cable performance, are contaminants in the insulation and protrusions in the semiconductor layer. Through modeling experiments, the authors determine the minimum breakdown strength of EMJ and use this to determine design values for 500 kV EMJ. Finally, they carry out breakdown tests on actual equipment, resulting in the prospect of the actual realization of 500 kV EMJ
Keywords
XLPE insulation; cable insulation; cable jointing; electric breakdown; extrusion; insulation testing; power cable testing; power cables; 500 kV; XLPE power cable; breakdown tests; contaminants; design; extrusion-molded joints; insulation; jointing techniques; minimum breakdown strength; modeling; performance; protrusions; semiconductor layer; Automated highways; Cable insulation; Cities and towns; Electric breakdown; Power cable insulation; Power cables; Testing; Underground power cables; Urban areas; Voltage;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/61.329508
Filename
329508
Link To Document