• DocumentCode
    1189497
  • Title

    Development of 500-kV XLPE cables and accessories for long distance underground transmission lines-Part II: jointing techniques

  • Author

    Kubota, Takeo ; Takahashi, Yoshihisa ; Hasegawa, Takaaki ; Noda, Hajime ; Yamaguchi, Masayuki ; Tan, Masayuki

  • Author_Institution
    Tokyo Electr. Power Co. Inc., Japan
  • Volume
    9
  • Issue
    4
  • fYear
    1994
  • fDate
    10/1/1994 12:00:00 AM
  • Firstpage
    1750
  • Lastpage
    1759
  • Abstract
    This paper reports on the results of a basic inquiry for the purpose of developing extrusion-molded joints (EMJ) for use with 500 kV XLPE power cable. The authors have made it clear that the factors that govern EMJ performance, like cable performance, are contaminants in the insulation and protrusions in the semiconductor layer. Through modeling experiments, the authors determine the minimum breakdown strength of EMJ and use this to determine design values for 500 kV EMJ. Finally, they carry out breakdown tests on actual equipment, resulting in the prospect of the actual realization of 500 kV EMJ
  • Keywords
    XLPE insulation; cable insulation; cable jointing; electric breakdown; extrusion; insulation testing; power cable testing; power cables; 500 kV; XLPE power cable; breakdown tests; contaminants; design; extrusion-molded joints; insulation; jointing techniques; minimum breakdown strength; modeling; performance; protrusions; semiconductor layer; Automated highways; Cable insulation; Cities and towns; Electric breakdown; Power cable insulation; Power cables; Testing; Underground power cables; Urban areas; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.329508
  • Filename
    329508