• DocumentCode
    1191217
  • Title

    Protection Zone for Buildings Against Lighning Strokes Using Transmission Line Protection Practice

  • Author

    Lee, Ralph H.

  • Author_Institution
    Lee Electrical Engineering, Inc., Wilmington, DE 19807.
  • Issue
    6
  • fYear
    1978
  • Firstpage
    465
  • Lastpage
    469
  • Abstract
    The nature of the zone of protection of structures from an elevated rod or wire, inadequately defined in the past, can be determined with high reliability using data developed by E.R.Whitehead of the Illinois Institute of Technology under contract from the Edison Electric Institute for the protection of high-voltage electric transmission lines. The vertical boundary of this zone of protection is not linear, as has been believed in the past, but is a circular arc, tangent to the ground, of 150-ft radius for 99.5 percent protection and 125-ft radius for 99.9 percent protection.
  • Keywords
    Buildings; Contracts; Engine cylinders; Industrial power systems; Lightning; Power system modeling; Power system protection; Shape; Transmission line theory; Wire;
  • fLanguage
    English
  • Journal_Title
    Industry Applications, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0093-9994
  • Type

    jour

  • DOI
    10.1109/TIA.1978.4503576
  • Filename
    4503576