• DocumentCode
    1195686
  • Title

    Designing to Avoid Hazardous Transferred Earth Potentials

  • Author

    Nichols, Neil ; Shipp, David D.

  • Author_Institution
    Engineering Service Office, Westinghouse Electric Corporation, Los Angeles, CA.
  • Issue
    4
  • fYear
    1982
  • fDate
    7/1/1982 12:00:00 AM
  • Firstpage
    340
  • Lastpage
    347
  • Abstract
    ``Grounding´´ is not an absolute phenomena, but rather a relative expression of conductivity to a common earth plane. Use of modifying adjectives such as ``effective´´ recognizes the existence of less than complete conductance. It follows that if current is conducted through these ground paths, a difference in potential will exist. When alternate conducting paths bring the potential from one location into proximity with the potential of another location, potential difference may exist across insulating elements which exceed their insulating capabilities and can be dangerous to personnel. this can involve primary, secondary, and control systems. Some case histories are presented, one of which has parameters that cause it to be particularly revealing of the basic problems involved.
  • Keywords
    Conductors; Earth; Electric resistance; Fault currents; Grounding; Impedance; Insulation; Roentgenium; Substations; Voltage;