• DocumentCode
    1195935
  • Title

    A Scalable Power-Line-Signaling-Based Scheme for Islanding Detection of Distributed Generators

  • Author

    Wang, Wencong ; Kliber, Jacek ; Xu, Wilsun

  • Author_Institution
    Dept. of Electr. & Comput. Eng., Univ. of Alberta, Edmonton, AB
  • Volume
    24
  • Issue
    2
  • fYear
    2009
  • fDate
    4/1/2009 12:00:00 AM
  • Firstpage
    903
  • Lastpage
    909
  • Abstract
    Power-line-signaling-based schemes are regarded as promising solutions to the problem of islanding detection of distributed generators (DGs). These schemes broadcast dedicated signals from the distribution substation to the downstream DGs and, therefore, transform the detection of islanded DGs into the determination of the signal presence at the DG sites. This paper presents an improvement to a published power-line-signaling method. With this improvement, the signaling device can be located anywhere between the substation and the DG sites, creating the opportunity for designing customized islanding detection arrangements for various DG interconnection scenarios. Simulations and laboratory tests show that the improved scheme can work reliably.
  • Keywords
    power distribution reliability; substations; distributed generators; distribution substation; islanding detection; scalable power-line-signaling; DG interconnection; Distributed generation (DG); islanding detection; power-line signaling;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/TPWRD.2008.2002688
  • Filename
    4802016