DocumentCode
1196092
Title
Extrapolation of measured power system response data to high-altitude EMP excitation
Author
Tesche, Frederick M. ; Barnes, Paul R.
Author_Institution
LuTech Inc., Greenville, TX, USA
Volume
30
Issue
3
fYear
1988
fDate
8/1/1988 12:00:00 AM
Firstpage
386
Lastpage
392
Abstract
Pulse injection measurements performed on an electrical generation plant in Sweden are reported. It is shown how these data may be used to calculate the high-altitude nuclear electromagnetic pulse (HEMP) response of the system when it is connected to the powergrid. It is found that the HEMP-induced current stages in overhead transmission lines are significantly attenuated as they propagate from the switch yard to the generator output terminals
Keywords
electromagnetic pulse; power plants; power system measurement; HEMP; HEMP-induced current stages; Sweden; electrical generation plant; high-altitude EMP excitation; measured power system response data; overhead transmission lines; powergrid; pulse injection measurements; switch yard; Electric variables measurement; Electromagnetic measurements; Extrapolation; Nuclear power generation; Power measurement; Power system measurements; Pulse measurements; Pulse power systems; Switches; Transmission line measurements;
fLanguage
English
Journal_Title
Electromagnetic Compatibility, IEEE Transactions on
Publisher
ieee
ISSN
0018-9375
Type
jour
DOI
10.1109/15.3319
Filename
3319