• DocumentCode
    1200119
  • Title

    Considerations in Testing and Stabilizing Frequency Beating of a Current Source Inverter

  • Author

    Min, Byung J. ; Jarc, Dennis A.

  • Author_Institution
    Research and Development Department, Reliance Electric Company, Collins Industrial Drive
  • Issue
    5
  • fYear
    1984
  • Firstpage
    1290
  • Lastpage
    1295
  • Abstract
    It is generally believed that the current-source inverter adjustable frequency controller with auto sequential commutation cannot be easily tested without a load motor connected. However, it is shown that the controller can, in fact, easily be tested without a load motor by adding some simple circuits in both the regulator and power circuit and by following step-by- step test procedures. The frequency beating phenomenon inherent in the current-source inverter and an effective compensating technique are also presented and explained.
  • Keywords
    Circuit testing; Commutation; Frequency; Industrial control; Industry Applications Society; Inverters; Meetings; Regulators; Sequential analysis; Voltage control;