DocumentCode
1215434
Title
Examination of the current injection technique [distribution networks]
Author
Taleb, M. ; Ortmeyer, T.H.
Author_Institution
Dept. of Electr. & Comput. Eng., Clarkson Univ., Potsdam, NY, USA
Volume
7
Issue
1
fYear
1992
fDate
1/1/1992 12:00:00 AM
Firstpage
442
Lastpage
448
Abstract
The limitations of the current injection technique are described. Time domain steady state simulation of the six pulse AC-DC converter in distribution systems is used as a model to determine those limitations. The simulation is able to operate under balanced or unbalanced circumstances. The time domain steady state simulation shows that the simple current injection technique is not a bad model for harmonic analysis if the converter operates under balanced conditions. If the converter is subject to irregular conditions, however, current injection might be inaccurate
Keywords
distribution networks; power convertors; 6-pulse AC-DC convertor; current injection; distribution networks; harmonic analysis; time domain steady state simulation; AC-DC power converters; Circuit simulation; Harmonic analysis; Power generation; Power system analysis computing; Power system dynamics; Power system harmonics; Power system modeling; Steady-state; Voltage;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/61.108939
Filename
108939
Link To Document