• DocumentCode
    1219413
  • Title

    Shielding Effectiveness of the Gas-Insulated Bus Duct for Transient EM Fields Generated in a GIS During Switching Operations

  • Author

    Rao, M. Mohana ; Thomas, M. Joy ; Singh, B.P.

  • Author_Institution
    Corp. R&D, Bharat Heavy Electr., Ltd., Hyderabad
  • Volume
    23
  • Issue
    4
  • fYear
    2008
  • Firstpage
    1946
  • Lastpage
    1953
  • Abstract
    Characterization and quantification of the transient electromagnetic (EM) fields generated in a gas-insulated substation (GIS) during switching operations has become important in recent years. This is due to increased use of sensitive electronic devices in the control circuitry of such substations. In this paper, a numerical model based on the finite-difference time-domain technique has been developed to compute the EM field emission from the gas-insulated bus duct through nonmetallic flange of the support insulator during switching operations. The shielding effectiveness (SE) of the bus duct/section for the EM fields has been evaluated using a derivative Gaussian current source and a short time sinusoidal current source. The effect of variations in dimensions of the slot formed by the nonmetallic flange as well as electromagnetic properties of the insulator/bus duct enclosure on SE has been studied. The variation in field pattern along the axis of bus duct at various distances due to the transient currents of different frequencies has been analyzed. The enhancement factor for the EM field levels due to the presence of a metallic structure has been reported. Finally, emission levels are calculated for the very fast transient currents generated in a 245 kV GIS and their dominant frequencies have been identified.
  • Keywords
    electromagnetic fields; finite difference time-domain analysis; gas insulated substations; GIS; Gaussian current source; control circuitry; electronic devices; enhancement factor; finite-difference time-domain technique; gas-insulated bus duct; gas-insulated substation; insulator-bus duct enclosure; metallic structure; numerical model; shielding effectiveness; sinusoidal current source; switching operations; transient EM fields; transient currents; transient electromagnetic fields; voltage 245 kV; Electromagnetic interference (EMI); gas-insulated substation (GIS); shielding effectiveness (SE); switching; very fast transient currents (VFTC);
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/TPWRD.2008.923065
  • Filename
    4520263