DocumentCode
1222671
Title
Exact voltage unbalance assessment without phase measurements
Author
Ghijselen, Jozef A L ; Van Den Bossche, Alex P M
Author_Institution
Dept. of Electr. Energy, Ghent Univ., Gent, Belgium
Volume
20
Issue
1
fYear
2005
Firstpage
519
Lastpage
520
Abstract
In this letter, it is shown that the positive- and negative-sequence components of a three-phase, sinusoidal and unbalanced voltage system can be calculated exactly without the application of the Fortescue transformations in the complex plane, while only the root mean square (RMS) line-to-line voltages are required, and without having to measure the phase relationships between these voltages. This results in a convenient procedure to assess voltage unbalance in the field. The phase relationships between the sequence and line components can also be calculated. Moreover, if the RMS values of the line-to-neutral voltages are known, the zero-sequence component can be calculated exactly as well, again, without the application of complex mathematics.
Keywords
mean square error methods; phase measurement; power supply quality; Fortescue transformations; line to line voltages; line to neutral voltages; phase measurement; power quality; root mean square; sinusoidal voltage; unbalanced voltage system; voltage unbalance assessment; zero sequence component; Automation; Clocks; Mathematics; Phase measurement; Power engineering and energy; Power systems; Root mean square; Voltage;
fLanguage
English
Journal_Title
Power Systems, IEEE Transactions on
Publisher
ieee
ISSN
0885-8950
Type
jour
DOI
10.1109/TPWRS.2004.841145
Filename
1388554
Link To Document