• DocumentCode
    1222671
  • Title

    Exact voltage unbalance assessment without phase measurements

  • Author

    Ghijselen, Jozef A L ; Van Den Bossche, Alex P M

  • Author_Institution
    Dept. of Electr. Energy, Ghent Univ., Gent, Belgium
  • Volume
    20
  • Issue
    1
  • fYear
    2005
  • Firstpage
    519
  • Lastpage
    520
  • Abstract
    In this letter, it is shown that the positive- and negative-sequence components of a three-phase, sinusoidal and unbalanced voltage system can be calculated exactly without the application of the Fortescue transformations in the complex plane, while only the root mean square (RMS) line-to-line voltages are required, and without having to measure the phase relationships between these voltages. This results in a convenient procedure to assess voltage unbalance in the field. The phase relationships between the sequence and line components can also be calculated. Moreover, if the RMS values of the line-to-neutral voltages are known, the zero-sequence component can be calculated exactly as well, again, without the application of complex mathematics.
  • Keywords
    mean square error methods; phase measurement; power supply quality; Fortescue transformations; line to line voltages; line to neutral voltages; phase measurement; power quality; root mean square; sinusoidal voltage; unbalanced voltage system; voltage unbalance assessment; zero sequence component; Automation; Clocks; Mathematics; Phase measurement; Power engineering and energy; Power systems; Root mean square; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8950
  • Type

    jour

  • DOI
    10.1109/TPWRS.2004.841145
  • Filename
    1388554