DocumentCode
1227627
Title
Pollution tests for coastal conditions on an 800 kV composite bushing
Author
Engelbrecht, Chris S. ; Hartings, Ralf ; Tunell, Helena ; Engström, Björn ; Janssen, Harald ; Hennings, Raimund
Author_Institution
STRI AB, Ludvika, Sweden
Volume
18
Issue
3
fYear
2003
fDate
7/1/2003 12:00:00 AM
Firstpage
953
Lastpage
959
Abstract
The dry salt layer pollution test method is introduced as a better alternative to the present standardized insulator test method for coastal environments. Comparative tests were performed on an 800 kV composite housed SF6 filled bushing, using the salt-fog and dry-salt-layer test methods. The two test methods are described and compared. Details of the external insulation of the 800 kV bushing are provided together with the results from the withstand tests performed. The discussion focuses on the mechanism of pollution deposit under each of the test methods and on the advantage that the dry salt layer method has when testing hydrophobic insulators.
Keywords
SF6 insulation; bushings; composite insulators; insulator contamination; insulator testing; 800 kV; SF6; SF6 filled bushing; coastal conditions; composite bushing; dry salt layer pollution test method; dry-salt-layer test; hydrophobic insulators testing; pollution tests; salt-fog test; standardized insulator test method; DSL; Environmentally friendly manufacturing techniques; Flashover; Glass; Insulator testing; Performance evaluation; Plastic insulation; Pollution; Polymers; Sea measurements;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/TPWRD.2003.813826