DocumentCode
1270537
Title
Abridgment of current transformer excitation: Under transit conditions
Author
Marshall, Donald ; Langguth, P.O.
Author_Institution
Westinghouse Elec. & Mfg. Co., East Pittsburgh, Pa.
Volume
48
Issue
12
fYear
1929
Firstpage
884
Lastpage
888
Abstract
Tests of circuit breakers, relays, and similar devices in which current transformers have been used to step down the large currents involved to values measurable by the oscillograph, have shown peculiar errors in the records during the transient portion of the current wave. The purpose of this paper is to show that the abnormal excitation of the magnetic circuit of the current transformer required during transient conditions is the cause of these errors, and to point out how the errors may be minimized sufficiently to be negligible. Mathematical expressions are also derived to make it possible to predetermine the ability of a transformer to handle transients correctly and to be a guide in the design of transformers for this service.
fLanguage
English
Journal_Title
A.I.E.E., Journal of the
Publisher
ieee
ISSN
0095-9804
Type
jour
DOI
10.1109/JAIEE.1929.6536499
Filename
6536499
Link To Document