Transformer derating for harmonic currents: a wide-band measurement approach for energized transformers
Author
Kelley, Arthur W. ; Edwards, Steven W. ; Rhode, Jason P. ; Baran, Mesut E.
Author_Institution
Dept. of Electr. & Comput. Eng., North Carolina State Univ., Raleigh, NC, USA
Volume
35
Issue
6
fYear
1999
Firstpage
1450
Lastpage
1457
Abstract
Power system transformers must often be derated when supplying harmonic currents to nonlinear loads. IEEE Recommended Practice C57.110 extrapolates transformer loss for harmonic frequencies based on DC winding resistance and rated eddy-current loss. This paper describes an improved derating technique based on direct measurements performed at fundamental and harmonic frequencies. The measurements can be performed regardless of whether the transformer is energized and in service or deenergized and out of service. For energized transformers, the measurement can be performed regardless of whether the transformer is fully loaded or unloaded. Measurements of several distribution transformers show the improvement of this method over C57.110
Keywords
IEEE standards; electric impedance measurement; harmonic distortion; load (electric); power supply quality; power system harmonics; power transformer testing; transformer windings; DC winding resistance; IEEE Recommended Practice C57.110; distribution transformers; energized transformers; harmonic currents; harmonic frequencies; improved derating technique; nonlinear loads; power transformer derating; rated eddy-current loss; wide-band measurement approach; Current measurement; Current supplies; Electrical resistance measurement; Energy measurement; Impedance measurement; Performance evaluation; Power measurement; Power system harmonics; Power system measurements; Wideband;
fLanguage
English
Journal_Title
Industry Applications, IEEE Transactions on
Publisher
ieee
ISSN
0093-9994
Type
jour
DOI
10.1109/28.806061
Filename
806061
Link To Document