• DocumentCode
    1271704
  • Title

    Surge investigations on overhead lines and cable systems

  • Author

    Melsom, S.W. ; Arman, A.N. ; Bibby, W.

  • Volume
    68
  • Issue
    407
  • fYear
    1930
  • fDate
    11/1/1930 12:00:00 AM
  • Firstpage
    1476
  • Lastpage
    1486
  • Abstract
    The paper describes measurements of surge voltages made under actual working conditions on 33-kV transmission lines both overhead, underground and composite. The apparatus used for the measurements was the klydonograph, and the paper gives a description of this instrument in its final form and a discussion of its working principles. The specially designed auxiliary condensers required to subdivide the line voltage are also described. Measurements on three important transmission systems covering a year or more of continuous recording are detailed. Generally there is a large amount of oscillatory surging set up by brushing at insulators when such insulators are in a dirty condition, the over-voltage being of very high frequency and of the order of three times the normal line voltage. The atmospheric conditions under which salt is deposited on insulators are described and some of the records show the effect on the line voltage of a salt-laden insulator up to the time at which flash-over occurred and the line was put out of operation. The question of porcelain insulators to meet the prevailing foul conditions and to avoid surges due to brushing is discussed. It is shown that with proper attention to design the voltage at which brushing commences can be materially increased, and it is suggested that this factor is of even greater importance than a very high initial flash-over voltage.
  • Keywords
    cables (electric); overhead lines; sparks; surges; voltage measurement;
  • fLanguage
    English
  • Journal_Title
    Electrical Engineers, Journal of the Institution of
  • Publisher
    iet
  • Type

    jour

  • DOI
    10.1049/jiee-1.1930.0158
  • Filename
    5315029