• DocumentCode
    1271855
  • Title

    Influence of Reactors on Input Harmonics of Variable Frequency Drives

  • Author

    Xiaodong Liang ; Ilochonwu, O. ; Lim, Jungyoul

  • Author_Institution
    Edmonton Product Center, Schlumberger, Edmonton, AB, Canada
  • Volume
    47
  • Issue
    5
  • fYear
    2011
  • Firstpage
    2195
  • Lastpage
    2203
  • Abstract
    AC line reactors and dc link reactors are widely used in variable frequency drives (VFDs) to improve the drive performance such as reducing input harmonics, improving the input power factor, and protecting the drives from surges, etc. The effectiveness of both types of reactors in reducing input harmonics is affected by many factors, including the loading of the drives and the system source impedance. In this paper, a simulation is conducted to investigate the influence of such factors. Two power distribution systems with VFDs as the dominant loads in the oil field are used as the case studies. The rules to evaluate the needs and effectiveness using ac line or dc link reactors are proposed for practical applications.
  • Keywords
    electric impedance; power harmonic filters; reactors (electric); variable speed drives; AC line reactors; VFD; dc link reactors; harmonic suppression; power distribution systems; system source impedance; variable frequency drives; Harmonic analysis; Impedance; Inductance; Inductors; Loading; Power system harmonics; AC line reactor; dc link reactor; input harmonics; power source impedance;
  • fLanguage
    English
  • Journal_Title
    Industry Applications, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0093-9994
  • Type

    jour

  • DOI
    10.1109/TIA.2011.2161858
  • Filename
    5953504