• DocumentCode
    1272772
  • Title

    Evaluation of the Guang Dong lightning location system with transmission line fault data

  • Author

    Chen, S.M. ; Du, Y. ; Fan, L.M. ; He, H.M. ; Zhong, D.Z.

  • Author_Institution
    Dept. of Electr. Eng., Tsinghua Univ., Beijing, China
  • Volume
    149
  • Issue
    1
  • fYear
    2002
  • fDate
    1/1/2002 12:00:00 AM
  • Firstpage
    9
  • Lastpage
    16
  • Abstract
    The Guang Dong lightning location system (GDLLS) was put into operation in 1997. Its performance, including detection efficiency and location accuracy, was evaluated with the data of the recorded lightning faults on 110, 220 and 500 kV transmission lines in 1997-1999. Lightning parameters, such as thunderstorm days, ground-flash density and peak lightning current were estimated with the lightning data collected by GDLLS. It is found that the detection efficiency is as high as 86%, and the median lightning accuracy is about 1.3 km. The correlation between the number of detected lightning flashes and recorded transmission line faults is weak, but can be improved if more appropriate analysis methods or data are employed
  • Keywords
    fault location; lightning; power transmission faults; power transmission lines; 110 kV; 220 kV; 500 kV; 86 percent; Guang Dong lightning location system; detection efficiency; ground flash density; location accuracy; peak current; thunderstorm day; transmission line fault;
  • fLanguage
    English
  • Journal_Title
    Science, Measurement and Technology, IEE Proceedings -
  • Publisher
    iet
  • ISSN
    1350-2344
  • Type

    jour

  • DOI
    10.1049/ip-smt:20020131
  • Filename
    995769