• DocumentCode
    1275990
  • Title

    Equivalent heat circuit based power transformer thermal model

  • Author

    Tang, W.H. ; Wu, Q.H. ; Richardson, Z.J.

  • Author_Institution
    Dept. of Electr. Eng. & Electron., Liverpool Univ., UK
  • Volume
    149
  • Issue
    2
  • fYear
    2002
  • fDate
    3/1/2002 12:00:00 AM
  • Firstpage
    87
  • Lastpage
    92
  • Abstract
    An equivalent heat circuit based thermal model of oil-immersed power transformers and a methodology for model construction using intelligent learning based on real-world data are presented. The proposed thermal model is established to calculate the real-time temperatures of the main parts of a natural oil, natural air (ONAN) and forced oil, forced air (OFAF) cooled power transformer, which is based on the principles of heat exchange and electric circuit laws. A genetic algorithm is used as a search method, based on a few onsite measurements, to determine the thermal model parameters.
  • Keywords
    cooling; power transformers; thermal analysis; transformer oil; equivalent heat circuit; forced air cooling; forced oil cooling; genetic algorithm; heat exchange; intelligent learning; model construction; natural air cooling; natural oil cooling; oil-immersed power transformers; power transformer thermal model; real-time temperatures natural oil; search method;
  • fLanguage
    English
  • Journal_Title
    Electric Power Applications, IEE Proceedings
  • Publisher
    iet
  • ISSN
    1350-2352
  • Type

    jour

  • DOI
    10.1049/ip-epa:20020290
  • Filename
    997798