• DocumentCode
    1285030
  • Title

    Circuit breakers for Boulder Dam line

  • Author

    Prince, D.

  • Author_Institution
    General Elec. Co. Philadelphia, Pa.
  • Volume
    54
  • Issue
    4
  • fYear
    1935
  • fDate
    4/1/1935 12:00:00 AM
  • Firstpage
    366
  • Lastpage
    372
  • Abstract
    Because of its length, 270 miles, the 275 kv transmission line from Boulder Dam to Los Angeles, Calif., requires extremely high speed switching for stability. To meet the requirements, a high voltage impulse circuit breaker, extending the oil blast theory to cover a multibreak construction with double cross-blast ports, has been built. It provides over-all switching times consistently less than 3 cycles (3/60 second). Approximately 10 per cent as much oil is used as in a comparable breaker of conventional design, and only 1/10 of this is exposed to arcing. Large factors of safety are provided over and above the interrupting rating of 5,000 amperes, 287 kv, or 2,500,000 kva.
  • fLanguage
    English
  • Journal_Title
    Electrical Engineering
  • Publisher
    ieee
  • ISSN
    0095-9197
  • Type

    jour

  • DOI
    10.1109/EE.1935.6539142
  • Filename