• DocumentCode
    1302681
  • Title

    Diagnosis of Onload Tap Changer Contact Degradation by Dynamic Resistance Measurements

  • Author

    Erbrink, Jur J. ; Gulski, Edward ; Smit, Johan J. ; Seitz, Paul P. ; Quak, B. ; Leich, Rory ; Malewski, Ryszard

  • Author_Institution
    Delft Univ. of Technol., Delft, Netherlands
  • Volume
    25
  • Issue
    4
  • fYear
    2010
  • Firstpage
    2121
  • Lastpage
    2131
  • Abstract
    Due to different degradation mechanisms, onload tap changers (OLTCs) may contribute to power transformer failures. If offline diagnosis is undertaken during functional checks performed during the service life of OLTC devices, some of the degradation effects can be assessed. This paper addresses an OLTC diagnostic method based on the measurement of dynamic resistance. An experimental investigation of the degraded OLTC contacts was used to identify a number of defects revealed by dynamic resistance measurements.
  • Keywords
    electric resistance measurement; fault diagnosis; on load tap changers; OLTC devices; OLTC diagnostic method; dynamic resistance measurements; onload tap changer contact degradation; power transformer failures; Contact resistance; Current measurement; Degradation; Electrical resistance measurement; Power transformers; Switches; Windings; Contact resistance; dynamic resistance measurement; dynamic response; onload tap changer; power transformers; selector contacts;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/TPWRD.2010.2050499
  • Filename
    5556038