• DocumentCode
    1327858
  • Title

    Fault gas generation in natural-ester fluid under localized thermal faults

  • Author

    Wang, Zhongdong ; Yi, Xiao ; Huang, Jinping ; Hinshaw, John V. ; Noakhes, John

  • Author_Institution
    Univ. of Manchester, Manchester, UK
  • Volume
    28
  • Issue
    6
  • fYear
    2012
  • Firstpage
    45
  • Lastpage
    56
  • Abstract
    In this article, the generation of fault gases in FR3 fluid was investigated under various thermal stresses using a sealed vessel with full fluid circulation, and the results were compared with Gemini X under similar conditions. The DGA measurements from an online dissolved-gas monitor were generally comparable with laboratory analysis. The FR3 is more thermally stable than Gemini X, as indicated by less free gas-bubble formation, less violent fluid convection, and less fault gas generation above 300°C.
  • Keywords
    bubbles; chemical analysis; organic compounds; power transformers; thermal power stations; thermal stresses; DGA measurements; FR3 fluid; dissolved-gas analysis; fault gas generation; full fluid circulation; gas-bubble formation; localized thermal faults; natural-ester fluid; online dissolved-gas monitor; sealed vessel; thermal stresses; violent fluid convection; Gas insulation; Generators; Heating; Power transformers; Temperature measurement; Thermal measurement; Duval triangle; dissolved-gas analysis; fault; gas generation; natural-ester oil; transformer; vegetable oil;
  • fLanguage
    English
  • Journal_Title
    Electrical Insulation Magazine, IEEE
  • Publisher
    ieee
  • ISSN
    0883-7554
  • Type

    jour

  • DOI
    10.1109/MEI.2012.6340524
  • Filename
    6340524