• DocumentCode
    1333218
  • Title

    On-load tap changer diagnosis - an off-line method for detecting degradation and defects: Part 1

  • Author

    Erbrink, Jur J. ; Gulski, Edward ; Smit, Johan J. ; Seitz, Paul P. ; Quak, Ben ; Leich, Rory ; Malewski, Ryszard A.

  • Author_Institution
    Delft Univ. of Technol., Delft, Netherlands
  • Volume
    26
  • Issue
    5
  • fYear
    2010
  • Firstpage
    49
  • Lastpage
    59
  • Abstract
    An advanced procedure for off-line power transformer diagnosis has been presented in this paper. Several different diagnostic measurements can be made using only one device. Examples and case studies were discussed to show the variety of defects and degradation mechanisms that can be detected using the procedure. In particular, it was found that the most common OLTC defects can be detected. The measurements are very sensitive to degradation due to long-term aging and to OLTC maintenance errors. A large population of OLTCs was tested, and a substantial number showed contact degradation. Finally, several areas that require careful attention were discussed, i.e., test current amplitude, circuit resistance, secondary short circuiting, and winding configuration.
  • Keywords
    fault diagnosis; on load tap changers; circuit resistance; contact degradation; defects detection; degradation detection; off-line method; on-load tap changer diagnosis; secondary short circuiting; test current amplitude; winding configuration; Electrical resistance measurement; Oil insulation; Power transformer insulation; Power transformers; Resistance heating; Switches; Windings; contact resistance; contacts; dynamic response; power transformer; resistance measurement;
  • fLanguage
    English
  • Journal_Title
    Electrical Insulation Magazine, IEEE
  • Publisher
    ieee
  • ISSN
    0883-7554
  • Type

    jour

  • DOI
    10.1109/MEI.2010.5585008
  • Filename
    5585008