DocumentCode
1333218
Title
On-load tap changer diagnosis - an off-line method for detecting degradation and defects: Part 1
Author
Erbrink, Jur J. ; Gulski, Edward ; Smit, Johan J. ; Seitz, Paul P. ; Quak, Ben ; Leich, Rory ; Malewski, Ryszard A.
Author_Institution
Delft Univ. of Technol., Delft, Netherlands
Volume
26
Issue
5
fYear
2010
Firstpage
49
Lastpage
59
Abstract
An advanced procedure for off-line power transformer diagnosis has been presented in this paper. Several different diagnostic measurements can be made using only one device. Examples and case studies were discussed to show the variety of defects and degradation mechanisms that can be detected using the procedure. In particular, it was found that the most common OLTC defects can be detected. The measurements are very sensitive to degradation due to long-term aging and to OLTC maintenance errors. A large population of OLTCs was tested, and a substantial number showed contact degradation. Finally, several areas that require careful attention were discussed, i.e., test current amplitude, circuit resistance, secondary short circuiting, and winding configuration.
Keywords
fault diagnosis; on load tap changers; circuit resistance; contact degradation; defects detection; degradation detection; off-line method; on-load tap changer diagnosis; secondary short circuiting; test current amplitude; winding configuration; Electrical resistance measurement; Oil insulation; Power transformer insulation; Power transformers; Resistance heating; Switches; Windings; contact resistance; contacts; dynamic response; power transformer; resistance measurement;
fLanguage
English
Journal_Title
Electrical Insulation Magazine, IEEE
Publisher
ieee
ISSN
0883-7554
Type
jour
DOI
10.1109/MEI.2010.5585008
Filename
5585008
Link To Document