• DocumentCode
    1338597
  • Title

    Evaluation of service aged 35 kV TR-XLPE URD cables

  • Author

    Katz, Carlos ; Walker, Michael

  • Author_Institution
    Cable Technol. Lab. Inc., New Brunswick, NJ, USA
  • Volume
    13
  • Issue
    1
  • fYear
    1998
  • fDate
    1/1/1998 12:00:00 AM
  • Firstpage
    1
  • Lastpage
    6
  • Abstract
    This paper provides information on the aging of URD power cable insulated with a tree-retardant crosslinked polyethylene (TR-XLPE) compound, installed in a typical utility environment, Numerous evaluations were performed on samples of power cables aged up to 7 years in-service. AC and impulse voltage breakdown data are compared with data for similar 35 kV ethylene propylene rubber (EPR) and crosslinked polyethylene (XLPE) insulated cables removed from the same utility system. The data show that, to date, the rate of degradation of TR-XLPE cables is less than that of the EPR and XLPE insulated cables. Extrapolation of the data, assuming the same rate, indicates TR-XLPE cable will have the longest life
  • Keywords
    XLPE insulation; ageing; electric breakdown; insulation testing; life testing; power cable insulation; power cable testing; underground cables; underground residential distribution systems; 35 kV; AC breakdown; URD cables; impulse voltage breakdown; power cable insulation testing; service ageing; tree-retardant crosslinked polyethylene; Aging; Cable insulation; Degradation; Dielectric breakdown; Paramagnetic resonance; Performance evaluation; Polyethylene; Power cables; Rubber; Trees - insulation;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.660836
  • Filename
    660836