• DocumentCode
    1339192
  • Title

    Calculation and measurement of winding disk capacitances with wound-in-shields

  • Author

    Vecchio, R. M Del ; Poulin, B. ; Ahuja, R.

  • Author_Institution
    North American Transformer, Milpitas, CA, USA
  • Volume
    13
  • Issue
    2
  • fYear
    1998
  • fDate
    4/1/1998 12:00:00 AM
  • Firstpage
    503
  • Lastpage
    509
  • Abstract
    The authors calculate the capacitance of a pair of power transformer winding disks containing wound-in-shields by means of a simple formula and by means of a detailed circuit model. In addition, experiments were performed to check the formula under various conditions such as changing the number of shield turns and attaching the shield to the high voltage terminal at different points or letting it float. Unlike a static capacitance calculation, these capacitances depend on inductive effects as is borne out in this study
  • Keywords
    capacitance; capacitance measurement; coils; power transformer testing; shielding; transformer windings; voltage distribution; circuit model; high voltage terminal; inductive effects; measurement; power transformer winding disks; shield turns number; winding disk capacitances; wound-in-shields; Capacitance measurement; Circuit testing; Coils; Drives; Interleaved codes; Joining processes; Labeling; Power cables; Voltage; Wounds;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.660921
  • Filename
    660921