• DocumentCode
    1354368
  • Title

    Equivalence of Influence of Pollution Simulating Methods on DC Flashover Stress of Ice-Covered Insulators

  • Author

    Jiang, Xingliang ; Chen, Ling ; Zhang, Zhijin ; Sun, Caixin ; Hu, Jianlin

  • Author_Institution
    State Key Lab. of Power Transm. Equip. & Syst. Security & New Technol., Chongqing Univ., Chongqing, China
  • Volume
    25
  • Issue
    4
  • fYear
    2010
  • Firstpage
    2113
  • Lastpage
    2120
  • Abstract
    The solid-layer method (SLM) and the icing-water- conductivity method (IWCM) are widely used in the insulator icing tests, but little research has been dedicated to the equivalence of these two methods. Based on the research on dc flashover performance of ice-covered insulators in the artificial climate chamber, this paper studied the equivalent relation between SLM and IWCM according to the equivalent principle of the flashover stress of ice-covered insulators. The results show that the influence of these two methods on flashover stress of iced insulator is equivalent, and this equivalence is determined by the configuration of insulator as well as the icing degree, but the icing flashover stress of the same type of insulators which are on the same pollution level simulated by the two different methods is consistent.
  • Keywords
    flashover; porcelain insulators; silicone rubber insulators; DC flashover stress; artificial climate chamber; ice covered insulator; icing water conductivity method; pollution simulating method; solid layer method; Flashover; Ice; Insulation; Insulator testing; Pollution; Power grids; Power transmission; Power transmission lines; Snow; Stress; DC flashover stress; equivalence; ice-covered insulators; pollution method;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/TPWRD.2009.2032329
  • Filename
    5352324