• DocumentCode
    136648
  • Title

    Research on on-line insulation monitoring and fault location method of mine power supply XLPE cable

  • Author

    Xudong Wang ; Tao Xia

  • Author_Institution
    Henan Polytech. Univ., Jiao Zuo, China
  • fYear
    2014
  • fDate
    Aug. 31 2014-Sept. 3 2014
  • Firstpage
    1
  • Lastpage
    4
  • Abstract
    Due to the dust, humidity and many other causes, the mine cable insulation will decrease gradually. This would cause leakage accidents and cable single-phase ground fault and then endanger the safety of the coal mines and workers. In order to solve above problems, this paper proposed a coal mine on-line insulation monitoring and fault location method. The way to achieve the goal is by superimposing a different frequency signal (DFS). When the operation of the cable is normal, it will monitoring the insulation condition of mine cable on-line, and when a single-phase ground fault occurs it will convert to locate the point of fault automatically. It combines the insulation monitoring and fault location in one system. The ATP/MATLAB simulation results show the feasibility and effectiveness of the method.
  • Keywords
    XLPE insulation; coal; fault location; leakage currents; power cable insulation; ATP-MATLAB simulation; DFS; XLPE cable; cable single-phase ground fault; coal mines; different frequency signal; fault location; leakage accidents; mine cable insulation; mine power supply; on-line insulation monitoring; Cable insulation; Fault location; Fuel processing industries; Monitoring; Power cables; Resistance;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Transportation Electrification Asia-Pacific (ITEC Asia-Pacific), 2014 IEEE Conference and Expo
  • Conference_Location
    Beijing
  • Print_ISBN
    978-1-4799-4240-4
  • Type

    conf

  • DOI
    10.1109/ITEC-AP.2014.6940919
  • Filename