  • Abstract
    Water is damaging for power transformers since it accelerates aging processes, reduces dielectric margin, decreases partial-discharge inception voltage, and, therefore, increases the probability of unexpected failures. Taking into account that power transformers are the most expensive equipment in an electrical plant and that the electrical supply guarantee is closely related to their reliability, it seems clear that transformer water content is a variable that must be kept under control. Since water is a byproduct of aging reactions in cellulosic insulation, the amount of water contained in a transformer usually increases from levels below 0.5% in weight, after its manufacturing, to levels of 6% in weight at the end of its life. However, it is not unusual to find high humidity levels in not so-old transformers, for example, in those that have been subjected to repairs in field. These days, some techniques are available to dry transformers in the field. Most of these methods achieve proper drying of transformer oil, but a great amount of water usually remains in cellulosic insulation and water in oil rises slowly some months after finishing the process. In these cases, drying treatments, which are very expensive, would have limited effectiveness. In this paper, a finite-element study is presented that analyzes different field-drying methods that are currently widely used. The efficiency of these methods will be studied and compared, and recommendations about drying parameters will be given.
  • Keywords
    partial discharges; power transformer protection; transformer oil; aging processes; aging reactions; cellulosic insulation; dielectric margin reduction; electrical plant; finite-element study; partial-discharge inception voltage; power transformers; transformer field drying procedures; transformer oil; transformer water content; unexpected failures probability; Accelerated aging; Dielectrics; Electric variables control; Finishing; Humidity; Manufacturing; Oil insulation; Petroleum; Power transformer insulation; Power transformers; Drying times; hot-oil drying; hot-oil spray drying; moisture in transformers; transformer field drying; transformer life management;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/TPWRD.2009.2027515
  • Filename
    5235732