• DocumentCode
    1369316
  • Title

    Application of GPT to tanδ measuring apparatus for distribution cable in hot line

  • Author

    Iga, A. ; Aihara, M. ; Fujiwara, Y. ; Kawai, J.

  • Author_Institution
    Shikoku Res. Inst. Inc., Takamatsu, Japan
  • Volume
    6
  • Issue
    3
  • fYear
    1991
  • fDate
    7/1/1991 12:00:00 AM
  • Firstpage
    938
  • Lastpage
    944
  • Abstract
    A hot line tanδ measuring apparatus which uses the secondary voltage of GPTs (grounding potential transformers) existing at substations and other facilities has been developed. An error vector circle diagram method which allows one to determine the value of tanδ to an accuracy of 0.1%, notwithstanding the phase difference existing between the primary and secondary voltages of a GPT, is described. The method was used in field experiments with favorable results. The method is especially superior in terms of safety and operability because no contact with high-voltage portions is required
  • Keywords
    potential transformers; power cables; voltage measurement; distribution cable; error vector circle diagram method; grounding potential transformers; hot line; operability; phase difference; primary voltage; safety; secondary voltage; substations; tanδ measuring apparatus; Cable insulation; Circuit testing; Current measurement; Dielectric measurements; Grounding; Power cables; Power measurement; Signal detection; Substations; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.85831
  • Filename
    85831