    Electrolytic corrosion of metal hardware of HVDC line and station insulators

  • Author

    Taniguchi, T. ; Watanabe, M. ; Watanabe, Y. ; Mori, S. ; Watanabe, Atsuyori ; Naito, K.

  • Author_Institution
    Central Res. Inst. of Electr. Power Ind., Yokosuka, Japan
  • Volume
    6
  • Issue
    3
  • fYear
    1991
  • fDate
    7/1/1991 12:00:00 AM
  • Firstpage
    1224
  • Lastpage
    1233
  • Abstract
    Insulators on HVDC lines may be damaged by or lose their mechanical strength because of electrolytic corrosion of the metal hardware. DC exposure tests of insulators have been conducted for 20 years at the Central Research Institute of Electric Power Industry in Japan. The authors describe the results of investigations of the electrolytic corrosion of the metal hardware of DC disk insulators with zinc-sleeved pins and cylindrical insulators and of the leakage electricity quantity flowing on their surface. Methods of life estimation of the metal hardware of insulators and corrosion prevention. The mechanism of hardware cracking of station-post insulators is clarified, and measures against the cracking are proposed
  • Keywords
    DC power transmission; cable insulation; corrosion testing; electric breakdown of solids; insulation testing; insulators; power cables; HVDC; Japan; corrosion prevention; cracking; electric breakdown; electrolytic corrosion; insulators; leakage electricity; life estimation; metal hardware; power cable insulation; Circuit testing; Corrosion; Dielectrics and electrical insulation; Electric variables measurement; HVDC transmission; Hardware; Insulator testing; Metal-insulator structures; Pollution measurement; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.85871
  • Filename
    85871