• DocumentCode
    1371226
  • Title

    Some fundamentals of equipment-grounding circuit design

  • Author

    Kaufmann, R. H.

  • Author_Institution
    General Electric Company, Schenectady, N. Y.
  • Volume
    73
  • Issue
    5
  • fYear
    1954
  • Firstpage
    227
  • Lastpage
    232
  • Abstract
    An effective equipment-grounding system should, under conditions of maximum ground-fault current flow, accomplish the following objectives: 1. maintain a low potential difference, perhaps 50 volts maximum, between machine frames, equipment enclosures, conductor enclosures, building metallic structure, and metallic components contained therein to avoid electric shock hazard and unwanted circulating current, and 2. incorporate adequate conductance to carry this maximum ground short-circuit current without thermal distress and the attendant fire hazard. There is good reason to believe that current flow in the equipment-grounding system in a-c power systems will not stray far from the power cable over which the outgoing current flows. It follows that the installation of conductive material in an equipment ground system unless properly located can be ineffective and wasteful, and can create a false sense of security. This paper presents the results of a special series of full-scale tests dealing with this specific problem and a general analysis of the circuit behavior.
  • Keywords
    Buildings; Conductors; Grounding; Joints; Sparks; Steel; Voltage measurement;
  • fLanguage
    English
  • Journal_Title
    American Institute of Electrical Engineers, Part II: Applications and Industry, Transactions of the
  • Publisher
    ieee
  • ISSN
    0097-2185
  • Type

    jour

  • DOI
    10.1109/TAI.1954.6371424
  • Filename