DocumentCode
1380659
Title
A Fault Location Technique for Two-Terminal Multisection Compound Transmission Lines Using Synchronized Phasor Measurements
Author
Liu, Chih-Wen ; Lin, Tzu-Chiao ; Yu, Chi-Shan ; Yang, Jun-Zhe
Author_Institution
Dept. of Electr. Eng., Nat. Taiwan Univ., Taipei, Taiwan
Volume
3
Issue
1
fYear
2012
fDate
3/1/2012 12:00:00 AM
Firstpage
113
Lastpage
121
Abstract
This paper presents a fault location technique for two-terminal multisection compound transmission lines, which combine overhead lines with underground power cables, using synchronized phasor measurements acquired by global positioning system (GPS) based phasor measurement units (PMUs) or digital relays with embedded PMU or by fault-on relay data synchronization algorithms. The technique is extended from a two-terminal fault location method with synchronized phasor measurements as inputs. A novel fault section selector is proposed to select the fault line section in advance. The proposed technique has the ability to locate a fault no matter where the fault is on overhead line or underground power cable. The adopted technique has a solid theoretical foundation and is direct and simple in terms of computational complexity. Both extensive simulation results and field test results are presented to demonstrate the effectiveness of the proposed scheme. The proposed technique has already been implemented in the Taiwan power system since the year 2008. Up to the present, the proposed technique yields excellent performance in practice.
Keywords
Global Positioning System; fault location; multiconductor transmission lines; power overhead lines; power system measurement; relay protection; underground cables; PMU; digital relays; embedded PMU; fault location; fault section selector; global positioning system; multisection compound transmission lines; overhead lines; phasor measurement units; relay data synchronization; synchronized phasor measurements; underground power cables; Compounds; Fault location; Impedance; Indexes; Power transmission lines; Synchronization; Transmission line measurements; Fault location; phasor measurement units (PMUs); two-terminal compound transmission lines;
fLanguage
English
Journal_Title
Smart Grid, IEEE Transactions on
Publisher
ieee
ISSN
1949-3053
Type
jour
DOI
10.1109/TSG.2011.2171198
Filename
6085617
Link To Document