DocumentCode
1398430
Title
Streamer propagation and breakdown under ac voltage in very large oil gaps
Author
Lesaint, O. ; Saker, A. ; Gournay, P. ; Tobazéon, R. ; Aubin, J. ; Mailhot, M.
Author_Institution
LEMD, CNRS, Grenoble, France
Volume
5
Issue
3
fYear
1998
fDate
6/1/1998 12:00:00 AM
Firstpage
351
Lastpage
359
Abstract
This paper presents a study of prebreakdown and breakdown phenomena under ac voltage in mineral oil in very large gaps (⩽80 cm). The investigations presented concern the measurement of breakdown voltages together with the recording of streamers in rod-plane and sphere-plane electrode systems, at different gap sizes. A breakdown mode specific to ac voltage is found, in which `bursts´ composed of streamers initiated at each half cycle appear. This mode leads to the lowest breakdown fields recorded under ac. Values of the average stress required for burst or direct breakdown modes are deduced from the experiments. Positive streamers are responsible for breakdown in large gaps: their propagation is easy and does not depend on the gap geometry and on the presence of particles. On the other hand, the propagation of negative streamers is quenched when not very divergent fields are used
Keywords
discharges (electric); electric breakdown; insulating oils; 80 cm; AC voltage; breakdown; burst mode; electrical stress; mineral oil gap; prebreakdown phenomena; rod-plane electrode system; sphere-plane electrode system; streamer propagation; Breakdown voltage; Electric breakdown; Electrodes; Geometry; Insulation; Minerals; Petroleum; Size measurement; Stress; Transformers;
fLanguage
English
Journal_Title
Dielectrics and Electrical Insulation, IEEE Transactions on
Publisher
ieee
ISSN
1070-9878
Type
jour
DOI
10.1109/94.689424
Filename
689424
Link To Document