• DocumentCode
    1403234
  • Title

    Unsynchronized Fault-Location Scheme for Nonlinear HIF in Transmission Lines

  • Author

    Ibrahim, Doaa Khalil ; El Sayed, T.E. ; El-Zahab, Essam El-Din Abou ; Saleh, Saber Mohamed

  • Author_Institution
    Electr. Power & Machines Dept., Cairo Univ., Cairo, Egypt
  • Volume
    25
  • Issue
    2
  • fYear
    2010
  • fDate
    4/1/2010 12:00:00 AM
  • Firstpage
    631
  • Lastpage
    637
  • Abstract
    The general aim of this paper is to develop an accurate fault-location scheme that can solve the problems affecting the accuracy of the existing conventional fault locators achieving easier maintenance and restoration time reduction as well as economical aims. This consequently helps to fit the new deregulation policies and competitive marketing. This investigation successfully applies zero-sequence current (3I 0) from the two terminals for earth high impedance fault (HIF) location, or negative-sequence currents from the two terminals of one faulted phase for line-to-line fault location. The HIF location is determined within only a maximum time of one cycle. The proposed scheme is insensitive to variations of different parameters, such as fault type, HIF behavior, wide-range transmission-line parameters variation, and fault inception angle. Staged fault testing results demonstrate that the proposed algorithm has feasible performance.
  • Keywords
    fault diagnosis; maintenance engineering; power transmission faults; power transmission lines; competitive marketing; deregulation policies; fault locators; nonlinear HIF; transmission lines; transmission-line parameters variation; unsynchronized fault-location scheme; zero-sequence current; Double-fed circuit; fault location; high impedance fault (HIF);
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/TPWRD.2009.2036182
  • Filename
    5406044