DocumentCode
1403276
Title
High-Frequency EHV/HV Autotransformer Model Identification From LEMP Test Data
Author
Delfino, Federico ; Procopio, Renato ; Rossi, Mansueto
Author_Institution
Dept. of Electr. Eng., Univ. of Genoa, Genoa, Italy
Volume
26
Issue
2
fYear
2011
fDate
4/1/2011 12:00:00 AM
Firstpage
714
Lastpage
724
Abstract
In this paper, the authors present a method to synthesize a power autotransformer model that takes into account high-frequency effects. The proposed procedure implements data usually available for this kind of transformer: the results of lightning electromagnetic pulse tests generally carried out on these machines in accordance with standard prescriptions. Furthermore, it makes use of a well-established model synthesis technique, namely, the fast relaxed vector fitting. A simple application example, involving lightning overvoltage effects, is also described in order to compare model behavior with simplified approaches.
Keywords
autotransformers; electromagnetic pulse; high-frequency transformers; high-voltage techniques; power system simulation; power transformer testing; LEMP test data; fast relaxed vector fitting; high-frequency EHV/HV autotransformer model identification; lightning electromagnetic pulse tests; model synthesis technique; power autotransformer model; Electromagnetic transients; identification; lightning electromagnetic pulse (LEMP) tests; power autotransformer; power system simulation;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/TPWRD.2009.2039151
Filename
5406050
Link To Document