DocumentCode
1403756
Title
Power Quality Investigation of Back-to-Back Harmonic Filters for a High-Voltage Anode Foil Manufacturing Facility
Author
Dionise, Thomas J. ; Lorch, Visuth ; Brazil, Brandon J.
Author_Institution
Power Syst. Eng. Dept., Eaton Corp., Warrendale, PA, USA
Volume
46
Issue
2
fYear
2010
Firstpage
694
Lastpage
702
Abstract
The problem, as described by this high-voltage anode foil manufacturing facility, has included loss of the harmonic filter banks during utility power disturbances. During such disturbances, one or more formation machine(s) trip and rectifier(s) fault, both of which are critical to the continuous operation of the process. One recent disturbance resulted in significant failure of components in both filter banks. A power quality investigation commenced to determine the cause of the filter bank failure. This paper describes the results of the analytical methods employed. Field harmonic measurements determined the presence of voltage and current distortion and established an appropriate model for harmonic analysis of various likely system conditions. Harmonic analysis explained the tuning of the existing filter banks and changes to tuning that have occurred since installation several years ago, as well as determined the harmonic loading on each stage of the filters. Transient simulations identified existing problems and areas of concern, particularly in regard to transient overvoltages that resulted when switching either of the filter banks. Recommendations included alternatives to avoid possible failures in the future, most significantly the redesign of one of the harmonic filters and the application of surge protection.
Keywords
harmonic distortion; power harmonic filters; power supply quality; back-to-back harmonic filters; current distortion; field harmonic measurements; filter bank failure; formation machine trip; high-voltage anode foil; high-voltage anode foil manufacturing facility; power quality investigation; surge protection; transient simulations; utility power disturbances; voltage distortion; Electromagnetic Transient Program (EMTP) simulations; IEEE Std. 18-1992; IEEE Std. 519-1992; harmonic analysis; harmonic filtering; power quality measurements;
fLanguage
English
Journal_Title
Industry Applications, IEEE Transactions on
Publisher
ieee
ISSN
0093-9994
Type
jour
DOI
10.1109/TIA.2010.2041091
Filename
5406119
Link To Document