• DocumentCode
    1419322
  • Title

    Switching-impulse flashover of air gaps and insulators in an artificially polluted atmosphere

  • Author

    Ely, C.H.A. ; Roberts, W.J.

  • Author_Institution
    CEGB, Central Electricity Research Laboratories, Leatherhead, UK
  • Volume
    115
  • Issue
    11
  • fYear
    1968
  • fDate
    11/1/1968 12:00:00 AM
  • Firstpage
    1667
  • Lastpage
    1671
  • Abstract
    Rod-rod and rod-plane gaps and a selection of insulators, mostly of dimensions relevant to 110¿132kV systems, have been subjected to switching impulses in artificial pollution. It has been shown that the flashover voltages of the gaps were little affected by the presence of fogs, either of water or of 120g/l salt solution. Substantial reductions, increasing with fog salinity, were found in the flashover voltages of the insulator surfaces. In highly saline fog, the flashover voltages were well under half the values for dry insulators. The preapplication of alternating service voltage to the polluted insulators always led to further reductions in flashover voltage.
  • fLanguage
    English
  • Journal_Title
    Electrical Engineers, Proceedings of the Institution of
  • Publisher
    iet
  • ISSN
    0020-3270
  • Type

    jour

  • DOI
    10.1049/piee.1968.0290
  • Filename
    5248908