    Harmonic resonance on parallel high voltage transmission lines

  • Author

    Harries, J.R. ; Randall, J.L.

  • Author_Institution
    Bonneville Power Adm., Portland, OR, USA
  • Volume
    12
  • Issue
    1
  • fYear
    1997
  • fDate
    1/1/1997 12:00:00 AM
  • Firstpage
    477
  • Lastpage
    482
  • Abstract
    Harmonic resonance has been observed, measured and modeled on parallel 500-kV lines that are about one wavelength at 2100 Hz, the 35th harmonic. A seemingly small harmonic injection at one location on the system causes significant problems some distance away such as telephone interference
  • Keywords
    electromagnetic interference; power system harmonics; power system measurement; power transmission lines; resonance; telephone interference; 2100 Hz; 35th harmonic; 500 kV; harmonic injection; harmonic resonance measurement; harmonic resonance modelling; parallel high voltage transmission lines; telephone interference; Capacitors; Interference; Lakes; Power transmission lines; Resonance; Substations; Telephony; Testing; Transmission lines; Voltage;