DocumentCode
1422672
Title
Harmonic resonance on parallel high voltage transmission lines
Author
Harries, J.R. ; Randall, J.L.
Author_Institution
Bonneville Power Adm., Portland, OR, USA
Volume
12
Issue
1
fYear
1997
fDate
1/1/1997 12:00:00 AM
Firstpage
477
Lastpage
482
Abstract
Harmonic resonance has been observed, measured and modeled on parallel 500-kV lines that are about one wavelength at 2100 Hz, the 35th harmonic. A seemingly small harmonic injection at one location on the system causes significant problems some distance away such as telephone interference
Keywords
electromagnetic interference; power system harmonics; power system measurement; power transmission lines; resonance; telephone interference; 2100 Hz; 35th harmonic; 500 kV; harmonic injection; harmonic resonance measurement; harmonic resonance modelling; parallel high voltage transmission lines; telephone interference; Capacitors; Interference; Lakes; Power transmission lines; Resonance; Substations; Telephony; Testing; Transmission lines; Voltage;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/61.568274
Filename
568274
Link To Document