• DocumentCode
    1432687
  • Title

    Protective relaying for multi-source generator buses

  • Author

    Simpson, Ronald H.

  • Author_Institution
    Gen. Electr. Co., Norcross, GA, USA
  • Volume
    26
  • Issue
    2
  • fYear
    1990
  • Firstpage
    330
  • Lastpage
    341
  • Abstract
    The reliability of an industrial power system can be increased by proper selection and application of protective relays. This is especially true for the medium-voltage distribution system. An effective protective relay application scheme is presented that uses devices widely used in present pulp and paper mill power distribution systems. The effective use of summation overcurrent and directional overcurrent relays for multisource generator buses makes it possible for the power system protective engineer to achieve good selective operation between source buses for both phase and ground fault current conditions. This greatly enhances the reliability of the power distribution system
  • Keywords
    distribution networks; overcurrent protection; paper industry; power system protection; relay protection; fault current; industrial power system; medium-voltage distribution system; multi-source generator buses; overcurrent; paper mill; pulp mills; relay protection; reliability; DC generators; Industrial power systems; Medium voltage; Paper mills; Power distribution; Power generation; Power system protection; Power system relaying; Power system reliability; Protective relaying;
  • fLanguage
    English